Asco 8025 Series Standard Photo
Asco 8025 Series Standard Photo

The Asco 8025B220 Solenoid Valve is designed for steam applications requiring secure shutoff during normal operation and a dependable trip-open response when power is lost. Its Latched Closed, No Voltage Release configuration ensures the valve remains closed while energized and opens only upon de-energization.

Technical Specifications

  • Valve Type: Manual Reset, Special Service Pilot, Latched Closed
  • Pipe Size: 3/4″
  • Flow Factor (Cv): 7.8
  • Operating Pressure Differential:
    • Steam: 5 to 125 psi
  • Maximum Fluid Temperature:
    • AC: 353°F (178°C)
    • DC: 353°F (178°C)
  • Body Material: Brass
  • Seal Material: PTFE Disc with EPDM, FPM, and PTFE Seals
  • Voltage Options:
    • AC (60Hz): 24, 120, 240, 480V
    • DC: 6, 12, 24, 120, 240V
  • Watt Rating:
    • AC: 20 watts
    • DC: 36.2 watts
  • Coil Insulation Class: F (AC), H (DC)
  • Solenoid Enclosure:
    • Standard: RedHat metal solenoid enclosure, Type 1 General Purpose Junction Box
    • Optional: Explosionproof and Watertight, Types 3, 7(C and D), and 9

Key Features and Functionality

  • Latched Closed Configuration: Remains sealed while the coil is powered.
  • Trip-Open Activation: Opens automatically when power is removed.
  • Steam-Compatible Design: It withstands high temperatures and saturated steam.
  • Compact System Integration: Ideal for tight installations in steam systems.
  • Manual Reset Enforcement: Must be manually reset after each trip.

Compatible Components and Related Parts

  • ASCO RedHat II Coil Series
  • ASCO Manual Reset Lever Kits
  • ASCO Seal Kit for 8025 Series
  • ASCO Explosionproof Solenoid Enclosure

Industry Applications

  • Autoclave Steam Inlets: Opens flow during power loss events.
  • Sterilizer Valve Panels: It maintains shutoff until the system signal fails.
  • Small Boiler Distribution: Trips open when energized power is interrupted.
  • Laundry Finishing Equipment: Flow enabled only after trip condition.
  • Thermal Lockout Circuits: Must be reset manually before operation resumes.

Compliance and Approvals

  • CSA Certified
  • Meets shock and vibration per ISA S71.03C2

Installation and Operational Notes

  • Mount in any orientation without flow impact.
  • Reset required after trip-open event.
  • Ensure clean, dry steam conditions.
  • Verify pressure and temperature compatibility.
  • Explosionproof setups must follow conduit sealing code.

Series Catalog

Asco 8015/8025 Manual Reset Valves

 

We ship these products worldwide! Delivery is normally stock.