The Asco 8017 002 Solenoid Operator is a high-powered pull-type operator for use in 2-way or 3-way valve configurations, capable of functioning as either normally open or normally closed. With increased coil wattage and a stronger magnetic pull curve than the Asco 8017 001, it is designed for high-force applications in general or hazardous areas requiring dependable actuation.
Technical Specifications
- Operator Type: 2-Way or 3-Way, Pull Type, Normally Open or Closed
- Construction Reference: 3B
- Watt Rating: 20.0 watts
- Coil Insulation Class: F
- VA Rating
- Holding: 43 VA
- Inrush: 90 VA
- Minimum Return Force: 1.75 lb
- Seal Material: NBR
- Voltage Options
- AC (60Hz): 24, 120, 240, 480V
- AC (50Hz): 110, 220V
- DC: 6, 12, 24, 120V
- Ambient Temperature Range
- AC: 32°F to 125°F (0°C to 52°C)
- DC: 32°F to 104°F (0°C to 40°C)
- Solenoid Enclosure
- Standard: RedHat – Type 1 (General Purpose)
- Optional: Explosionproof & Raintight (Types 3, 7, 9)
Key Features and Functionality
- Maximum Stroke Strength: Highest pull force in 8017 series.
- High Energy Coil: 20-watt Class F winding for aggressive actuation.
- Dual Valve Compatibility: Supports both 2-way and 3-way designs.
- Versatile Configuration: Operates in NO or NC roles.
- NEMA Housing Options: Explosionproof and raintight upgrades are available.
Compatible Components and Related Parts
- ASCO 8017 Series Valve Bodies (2-way and 3-way direct acting)
- ASCO High-Power RedHat Coils
- ASCO Explosionproof Enclosure Kits (EF Prefix)
- ASCO Operator Return Springs
- ASCO Mounting Plates and Fasteners
Industry Applications
- Valve Actuation Systems: For pressurized or dense flow media.
- Process Automation: High stroke force for rapid switching cycles.
- Control Cabinets: Integrated within multi-valve manifolds.
- Hazardous Facilities: Explosionproof-ready with optional housing.
- Heavy Duty OEM Builds: Used in custom-built valve systems.
Compliance and Approvals
-
CSA Certified
Installation and Operational Notes
- The return spring must counter a 1.75 lb force minimum.
- Orientation can be vertical or horizontal.
- Ensure the enclosure type matches the site classification.
- Suitable for high-cycle or aggressive duty loads.
- Match coil wattage to system power allowance.