The Allen Bradley 5094‑OF8IH is an isolated, 8-channel analog output module (current/voltage/HART) for the Compact 5000/Flex 5000 I/O system.
Technical Specifications
- Model: 5094‑OF8IH
- Channels: 8 isolated analog outputs
- Output Ranges: ±10 V, 0–5 V, 0–10 V; 0–20 mA, 4–20 mA with HART support
- Resolution: 16-bit
- Field Power: 18–32 V DC (SA)
- Backplane Power: 15 V DC @ ≤75 mA
- Isolation: 250 VAC field-to-backplane and between channels
- Operating Temperature: –40 °C to +70 °C
- Certifications: ATEX, IECEx, UL, Hazardous Location, ODVA, HART certified
- Conformal Coating: XT variant available
- Lifecycle Status: Active
Key Features
- Wide output range for current, voltage, and HART-enabled devices
- High-resolution performance with 16-bit precision
- Hot-swappable via RTB base (with field power off)
- Supports hot-swapping and is factory sealed for harsh environments
Compatible Components & Accessories
- 5094‑MBXT chassis and RTB3/RTB3XT terminal bases
- 5094‑STB shield bar (recommended for analog noise control)
- Studio 5000 Logix Designer for configuration and HART setup
- CompactLogix or Flex 5000 controllers via backplane
Industry Applications
- Process and loop control in chemical, energy, and manufacturing
- HART device integration and advanced diagnostics
- Rugged analog control in harsh or hazardous environments
Installation & Maintenance Notes
- Field-side power (SA) must be 18–32 V DC; remove before hot swap
- Use shielded twisted-pair cable (e.g., Belden 8761) for analog outputs
- Ensure conformal-coated slots remain sealed when not in use
- Use RAUP-enabled terminal base for safe in-service removal
Request a Quote
For pricing and availability, please Contact Us or call 1‑800‑755‑2883.
Disclaimer: TCI Supply is not an authorized Allen Bradley Distributor.
Frequently Asked Questions
Does this module support HART-enabled devices?
Yes—it features isolated HART output in 4–20 mA mode, fully compatible with HART transmitters.
Can I swap it while the system is running?
Yes—using the RTB base’s RIUP capability allows hot-swapping with field power off to avoid arcing.