Allen Bradley 5094-OF8

The Allen Bradley 5094‑OF8 is an 8‑channel analog current/voltage output module for the Compact 5000/Flex 5000 I/O system.

Technical Specifications

  • Model: 5094‑OF8
  • Series: Compact 5000 / Flex 5000 (5094)
  • Channels: 8 single-ended analog outputs
  • Output Ranges: 4–20 mA, 0–20 mA, 0–5 V, 0–10 V, ±10 V
  • Resolution: 16-bit
  • Drive Capability: ≥ 1 kΩ (voltage mode), ≤ 500 Ω (current mode)
  • Power: 15 V DC backplane, 18–32 V DC field-side
  • Ambient Temp: –40–70 °C operating
  • Isolation: 250 VAC field-to-backplane (non-isolated between channels)
  • Certifications: ATEX, IECEx, UL, hazardous-location rated
  • Conformal Coating: XT variant available for harsh environments
  • Lifecycle Status: Active

Key Features

  • High-density analog outputs—voltage or current selectable
  • Factory calibrated with optional user calibration
  • Support for both current and voltage output modes with diagnostics
  • RIUP-enabled removable terminal base allows hot-swapping (with field power removed)
  • Designed for rugged use with conformal-coated XT option

Compatible Components & Accessories

  • 5094‑MBXT chassis and RTB3/RTB3XT terminal bases
  • 5094‑STB shield bar (recommended for analog modules)
  • Studio 5000 Logix Designer for configuration and wiring tools
  • Flex 5000 or CompactLogix controllers via backplane

Industry Applications

  • Process/loop control in manufacturing and processing environments
  • Analog-driven controls in packaging, bottling, and energy systems
  • Harsh industrial zones requiring high-density analog I/O

Installation & Maintenance Notes

  • SA field power must be 18–32 V DC, ≤260 mA
  • Remove SA before swapping modules to prevent arcing
  • Use shielded twisted-pair wiring (e.g. Belden 8761) for noise immunity
  • Maintain conformal coating integrity by sealing unused slots
  • Use RTB with RIUP lever for safe hot-swapping

Request a Quote

For pricing and availability, please Contact Us or call 1‑800‑755‑2883.

Disclaimer: TCI Supply is not an authorized Allen Bradley Distributor.

Frequently Asked Questions

Can this module operate in voltage mode?

Yes—it supports voltage outputs (±10 V, 0–5 V, 0–10 V) with ≥1 kΩ load capability.

Can it be hot-swapped?

Yes—when using the RIUP terminal base, you can swap the module with field power removed, maintaining wiring integrity.

Is corrosion protection available?

Yes—conformal-coated “XT” variants provide added protection in harsh industrial environments.

Get A Quote

Fill in the form below, or call us now at 1-800-755-2883

"*" indicates required fields

This field is for validation purposes and should be left unchanged.