The Allen Bradley 5094‑OF8 is an 8‑channel analog current/voltage output module for the Compact 5000/Flex 5000 I/O system.
Technical Specifications
- Model: 5094‑OF8
- Series: Compact 5000 / Flex 5000 (5094)
- Channels: 8 single-ended analog outputs
- Output Ranges: 4–20 mA, 0–20 mA, 0–5 V, 0–10 V, ±10 V
- Resolution: 16-bit
- Drive Capability: ≥ 1 kΩ (voltage mode), ≤ 500 Ω (current mode)
- Power: 15 V DC backplane, 18–32 V DC field-side
- Ambient Temp: –40–70 °C operating
- Isolation: 250 VAC field-to-backplane (non-isolated between channels)
- Certifications: ATEX, IECEx, UL, hazardous-location rated
- Conformal Coating: XT variant available for harsh environments
- Lifecycle Status: Active
Key Features
- High-density analog outputs—voltage or current selectable
- Factory calibrated with optional user calibration
- Support for both current and voltage output modes with diagnostics
- RIUP-enabled removable terminal base allows hot-swapping (with field power removed)
- Designed for rugged use with conformal-coated XT option
Compatible Components & Accessories
- 5094‑MBXT chassis and RTB3/RTB3XT terminal bases
- 5094‑STB shield bar (recommended for analog modules)
- Studio 5000 Logix Designer for configuration and wiring tools
- Flex 5000 or CompactLogix controllers via backplane
Industry Applications
- Process/loop control in manufacturing and processing environments
- Analog-driven controls in packaging, bottling, and energy systems
- Harsh industrial zones requiring high-density analog I/O
Installation & Maintenance Notes
- SA field power must be 18–32 V DC, ≤260 mA
- Remove SA before swapping modules to prevent arcing
- Use shielded twisted-pair wiring (e.g. Belden 8761) for noise immunity
- Maintain conformal coating integrity by sealing unused slots
- Use RTB with RIUP lever for safe hot-swapping
Request a Quote
For pricing and availability, please Contact Us or call 1‑800‑755‑2883.
Disclaimer: TCI Supply is not an authorized Allen Bradley Distributor.
Frequently Asked Questions
Can this module operate in voltage mode?
Yes—it supports voltage outputs (±10 V, 0–5 V, 0–10 V) with ≥1 kΩ load capability.
Can it be hot-swapped?
Yes—when using the RIUP terminal base, you can swap the module with field power removed, maintaining wiring integrity.
Is corrosion protection available?
Yes—conformal-coated “XT” variants provide added protection in harsh industrial environments.