The Allen Bradley 5094‑OF4IHS is a 4‑channel isolated HART-enabled analog output module for the Compact 5000/Flex 5000 I/O system.
Technical Specifications
- Model: 5094‑OF4IHS
- Series: Compact 5000 / Flex 5000 (5094)
- Type: Analog output (current/voltage/HART)
- Channels: 4 isolated outputs
- Output Ranges: ±10 V, 0–10 V, 0–20 mA, 4–20 mA, with HART support
- Resolution: 16-bit
- Isolation: 250 VAC channel-to-channel and channel-to-backplane
- Supply Voltage: 18–32 V DC (field), 15 V DC (backplane)
- Power Consumption: ≤260 mA field-side, 75 mA backplane-side
- Ambient Temperature: –40 to +70 °C operating; –40 to +85 °C storage
- Certifications: ATEX, IECEx, UL, Hazardous Location rated, SIL 3 / PLe capable
- Lifecycle Status: Active
Key Features
- Isolated, 4-channel analog outputs with HART protocol support
- High-resolution 16-bit performance and flexible signal ranges
- SIL 3 / Performance Level PLe safety certification
- Hot-swappable via removable terminal base, designed for harsh environments
- Compatible with Flex 5000 shield bar for improved noise immunity
Compatible Components & Accessories
- 5094‑MBXT base and associated terminal blocks (e.g., RTB3ISXT)
- CompactLogix/Flex 5000 controllers via Compact 5000 backplane
- 5094‑STB shield bar accessory
- Studio 5000 Logix Designer & PanelView Plus HMIs
Industry Applications
- Process and loop control in chemical, energy, and water treatment plants
- HART-enabled device control in safe and certifiable environments
- Analog output in packaging, bottling, and machine control systems
Installation & Maintenance Notes
- Field-side power (SA) must be 18–32 V DC; wire shield to ground
- Ensure backplane in PID bank is energized before hot-swapping
- Remove module from base prior to field-side power removal to avoid arcing
- Bring shield bar to home earth ground when using shielded cables
Request a Quote
For pricing and availability, please Contact Us or call 1‑800‑755‑2883.
Disclaimer: TCI Supply is not an authorized Allen Bradley Distributor.
Frequently Asked Questions
Is it safety-certified?
Yes—the OF4IHS is SIL 3 / PLe certified and approved for hazardous locations.
Does it support HART communication?
Yes—HART-enabled for advanced field device control and diagnostics.
Can I hot-swap the module?
Yes—you can hot-swap via its removable terminal base, provided safety protocols are followed.