The Allen Bradley 5094‑IF8IH is an 8‑channel isolated analog input module (current/voltage/HART/RTD/TC) for the Compact 5000/Flex 5000 I/O system.
Technical Specifications
- Model: 5094‑IF8IH
- Channels: 8 isolated analog inputs
- Input Ranges: ±10 V, 0–10 V, 0–5 V; 0–20 mA, 4–20 mA; supports HART
- RTD & Thermocouples: Compatible with J, K, T, B, E, N, R, S and 2/3/4-wire RTDs
- Resolution: 24‑bit multiplexed ADC
- Field Power: 18–32 V DC via terminal base
- Backplane Power: 15 V DC @ ≤75 mA
- Isolation: 250 VAC field-to-backplane and between channels
- Ambient Temperature: –40–70 °C operating; –40–85 °C storage
- Certifications: ATEX T4, IECEx, UL, hazardous location rated
- Conformal Coating: XT variant available for harsh environments
- Lifecycle Status: Active
Key Features
- Highly flexible input module supporting voltage, current, RTD, thermocouple, and HART devices
- Isolated architecture ensures clean signal and eliminates ground loops
- Support for hot-swap via terminal base with RIUP lever
- Field-side shield bar ensures robust noise immunity
Compatible Components & Accessories
- 5094‑MBXT chassis with RTB3 or RTB3XT terminal bases
- 5094‑STB shield bar for field-side shielding
- Studio 5000 Logix Designer (v24 or newer for HART support)
- CompactLogix/Flex 5000 controllers
Industry Applications
- Process control systems with mixed analog signals
- HART-capable device integration in petrochemical and utility industries
- Harsh-environment analog sensing in manufacturing or field installations
Installation & Maintenance Notes
- Use shielded twisted-pair wiring for analog quality
- Connect SA field power correctly before hot-swapping
- Disconnect SA before removing RTB to avoid arcing
- Ensure conformal-coated ports remain sealed when idle
Request a Quote
For pricing and availability, please Contact Us or call 1‑800‑755‑2883.
Disclaimer: TCI Supply is not an authorized Allen Bradley Distributor.
Frequently Asked Questions
Can this module read thermocouples directly?
Yes—it supports most thermocouple types (J, K, T, B, E, N, etc.) and RTDs via built-in cold-junction compensation.
Is HART communication supported?
Yes—the module includes HART AOP support for compatible field transmitters.
Can I replace while powered?
Yes—with RIUP lever capability—but you must turn off SA field power first to prevent arcing.